Engineering via SICAM WEB
386 Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
DC8-037-2.02, Edition 10.2017
Processing type Parameter Meaning
RS_Mon_Source Source of state information for state infor-
mation monitoring
• Peripherals
• Open-/closed loop control function
• Both (logical OR)
Sw_Seq_command_seq Switching sequence: output additional com-
mand before or after the command
Sw_Seq_addtl_com Switching sequence: Select the additional
command
SID-BSE Source identification basic system element
SID-ST Source identification station number if mul-
tipoint traffic mode 0…99 if R-SID 0…254; if
automatic, the SID will be learned
SID-SSE Source identification supplementary system
element
QOC>8 If QOC > 8 (Qualifier of Command) is accept-
ed, so all QOC > 8 will be interpreted as
QOC = 0
RS_Image Parameter works only with ACP 1703 platform
DO_SI – digital output –
single-point information
receive_format Source of datapoint
Fail_behav Behavior at failure
SID-BSE Source identification basic system element
SID-ST Source identification station number if mul-
tipoint traffic mode 0…99 if R-SID 0…254; if
automatic, the SID will be learned
SID-SSE Source identification supplementary system
element
DO_SX – single-point
information and single
command output
receive_format Source of datapoint
Fail_behav Behavior at failure
• Keep
• Terminate
SID-BSE Source identification basic system element
SID-ST Source identification station number if mul-
tipoint traffic mode 0…99 if R-SID 0…254; if
automatic, the SID will be learned
SID-SSE Source identification supplementary system
element
select_execute_t Max. time between select and execute (in
seconds). After this time a recent select com-
mand is necessary.
0 = no select command is expected (direct
command transmission)
0 to 6553.5
RS_Image_CASDU1 Address of corresponding return state infor-
mation (S)
0 to 255
RS_Image_CASDU2 Address of corresponding return state infor-
mation (S)
0 to 255
RS_Image_IOA1 Address of corresponding return state infor-
mation (S)
0 to 255