Commissioning of I/O card (remote transmission) FCI2007
A1 and I/O card (horn/monitore
20
109 |
Building Technologies
20 Commissioning of I/O card (remote
transmission) FCI2007-A1 and I/O card
(horn/monitored) FCI2009-A1
With the I/O card (remote transmission) FCI2007-A1 and I/O card (horn /
monitored) FCI2009-A1, the monitored outputs are monitored for short-circuit and
open line. The resistance values of the lines may be read in and stored at the push
of a button. If a deviation from the quiescent value is detected, the control panel
evaluates a short-circuit or an open line.
The following outputs must be calibrated upon commissioning:
● FCI2007-A1: 'OUT1' to 'OUT3'
● FCI2009-A1: 'OUT1' to 'OUT8'
You will find more information about the FCI2007-A1 and FCI2009-A1 I/O cards
and planning monitored outputs in documents A6V10210362 and A6V10210368.
See chapter 'Applicable documents'.
FCI2007-A1 FCI2009-A1
S501 Button
Procedure
1. Check the connected lines for short-circuit and open line.
2. Connect the lines.
a During the commissioning of the control panel, fault messages are
indicated, provided that there are any deviations from the basic settings.
3. Press the S501 button.
a The resistance values are read in.
You can also read in the resistance values via the control panel's
Machine Interface.