Updating the firmware
Station: Updating the FW of the main CPU and additional CPUs
22
116 | 178
Building Technologies
A6V10210416_j_en_
--
Fire Safety
2018
-
-
29
22.2.3 Updating several 'Stations' simultaneously
You can update the firmware of max. eight networked 'Stations' simultaneously.
The 'Stations' and the CPU cards must be connected to one another via C-
WEB/LAN.
Example: Several 'Stations' are connected to each other via one or several
'Ethernet switch (MM) FN2008-A1'.
You will find additional information about the individual steps on the specified
pages.
w You are familiar with the information in chapter 'Preparation and security
[ 113]'.
w A GAP with DHCP must be configured for the connection with the PC via C-
WEB/LAN.
w The 'Stations' are displayed together.
w You can update not more than eight 'Stations' simultaneously.
1. Import the new firmware into Cerberus-Engineering-Tool.
Select the 'File' > 'Import new resource package' menu item and open the
file you want.
2. Load the configuration from the 'Station' or your archive to the PC. Link [ 32]
3. NOTICE! Data loss. Save the configuration data before updating the firmware.
Saving the configuration data also backs up specific system data which is
only available on the 'Station'. This includes modified customer texts, time
stamps of recent alarms, or persistent commands.
4. Convert the configuration if necessary and rectify conversion faults. Link
[ 128]
5. Connect the PC to the Ethernet switch (MM) FN2008-A1.
6. Update the firmware on the main CPU and the additional CPUs. Link [ 117]
Set each 'Station' individually in update mode. You can set the 'Stations' in
update mode without any waiting time one directly after the other.
Wait until the update of each 'Station' is completed.
7. Initialize each 'Station' individually. Link [ 28] To do so, you must connect the
PC to each 'Station' locally. Link [ 27]
8. Test the firmware version on the additional CPUs on each 'Station'. Link
[ 129]
Update the firmware, if required, of the additional CPUs again, if there is a
higher firmware version available. Link [ 126]
9. Disconnect the PC from the 'Station'. Link [ 27]
10. Restore the network connection, if required.