Connectivity and communication with 'Station'
Network parameter
s
4
26 | 178
Building Technologies
A6V10210416_j_en_
--
Fire Safety
2018
-
-
29
5. Set the following values:
'Protocol type': 'UDP'
'Local port': 'Specific Ports', and enter the value range '50067-50070' in the
box.
'Remote port': 'All Ports'
6. Confirm with 'OK'.
a The new firewall rule is now configured.
NOTICE
Security vulnerability in operating system due to open ports
Unauthorized access to your PC
Deactivate the firewall rule configured above after the firmware update.
4.2 Network parameters
Ports in FS720
Use Port number
Transport
protocol
Application
protocol
Comment
Communication
Station-to-station
communication
50501 UDP C-WEB
Communication between
Engineering Tool and
station
51000 UDP C-WEB
Communication between
management station and
FS720 station
47808-47823 UDP BACnet Dependent on configuration
Between BAC0 and BACF by
default
Monitoring
Station to station 50502 UDP C-WEB
Remote access via cRSP
Between Engineering Tool
and station
51001-51250 UDP C-WEB Dependent on configuration
Rule for ports: portHost =
51000 + hostID
Firmware update
Engineering tool 50067 UDP FW update
Panel 50068 UDP FW update
Engineering tool 50069 UDP FW update
Engineering tool 50070 UDP FW update