Updating the firmware
Testing the firmware version of the additional CPUs
22
129 |
178
Building Technologies
A6V10210416_j_en_
--
Fire Safety
2018
-
-
29
22.6 Testing the firmware version of the additional CPUs
If you have updated the firmware of the main CPU and the additional CPUs in a
single step ('FW update main and additional CPUs'), you must then test the
firmware version of the additional CPUs to ensure that the CPUs were updated
correctly. Update the firmware, if required, of the additional CPUs again, if there is
a higher firmware version available.
To test the firmware version on the additional CPUs, proceed as follows:
1. Select 'Update' > 'FW update additional CPUs' from the menu bar.
2. If the 'Password check' window opens, enter the password '12345678' and click
on 'OK'.
a The following window is opened:
3. Select the connection type:
Select 'Local connection' to establish a connection to the connected
standalone or SAFEDLINK 'Station'.
Select 'Connection to GAP' to establish a connection via GAP to a
networked 'Station'. In the field 'Target station address' enter the address
of 'Station'. If you want to create a connection to GAP 'Station' itself, enter
'0'.
4. Click on 'OK'.
a The following window is opened.
5. Test the firmware version on the additional CPUs.
6. Click on 'Cancel' in the 'FW update additional CPUs' window.