23.5 Test system data
System test manual
Ensure that the system test manual is available and up to date.
Remote transmission
Check that the phone numbers and the names of the remote transmission
receivers are up to date.
Data backup for 'Site'
1. Check that the system data are saved.
a Two copies must be archived with the ↑ 'Site', one copy with the technical
department.
2. Update the system data when the configuration is changed.
3. Note the date of execution in the system test manual.
Firmware
1. Read out the current firmware version from the ↑ 'Station': To do this, select
'Topology' > ↑ 'Hardware tree' > 'Station' > 'More Options' > 'Show details' in
the main menu.
2. Do not replace the current firmware version with the latest version unless this is
necessary to correct faults or add functions.
'Event memory'
Check the content of the 'Event memory' and take the necessary measures, e.g.,
switch on elements that have been switched off temporarily.
Change in use
Verify whether a change of use or changes to the building have an effect on the
configuration and perform the necessary corrections.
Pending modification applications
Check that all pending modification applications such as corrections to the
diagrams or modifications to the fire brigade orientation plans have been
completed.