ing Ethernet switch (MM) FN2008
A1 using Internet browser
16
89 |
Building Technologies
16.3 Configuring FN2008-A1 using Internet browser
A configuration is available via the localization manager. We recommend using
the configuration and if necessary making system-specific adaptations.
NOTICE
Incorrect settings of the ports
Malfunction
The factory setting 'auto
negotiation' for the ports may not be changed.
WARNING
System manipulation due to unauthorized access
No alarm in a fire.
● Change the preset password.
● Create a password as per the IT security requirements from Siemens; see
chapter 'Password guidelines'.
1. Open the Internet browser and enter the FN2008-A1's IP address in the
address field.
a The login window opens.
2. Login:
– User name = 'admin'
– Password = 'admin'
3. Select 'System' > 'Passwords' in the tree view and set a new password for the
following fields:
– 'New User Password'
– 'New Admin Password'
4. Confirm the entered password with 'Confirmation'.
5. Click 'Set Values'.
6. Select 'X204-2' > 'Ring' in the tree view and check the 'Enable ring redundancy'
checkbox.
– Select the 'Automatic Redundancy Detection' redundancy mode.
7. Select 'X204-2' > 'Fault Mask' in the tree view and check the
'Enable Link Down Monitoring' checkbox for each connected port:
– Port 5 and 6 = Ring
– Port 1 = The connected ↑ 'Station'
– Port 2 to 4 only if more stations 'Stations' are connected
a FN2008-A1 is configured.