Updating the firmware
Station: Updating the FW of the additional CPUs only
22
125 |
178
Building Technologies
A6V10210416_j_en_
--
Fire Safety
2018
-
-
29
22.3 Station: Updating the FW of the additional CPUs
only
If the 'Station' firmware is up to date and components have been changed, then it
is only necessary to update the additional CPUs. The procedure for updating the
firmware depends on the 'Station' function. The procedures are described in the
following chapters.
22.3.1 Standalone station and SAFEDLINK station
You will find additional information about the individual steps on the specified
pages.
w You are familiar with the information in chapter 'Preparation and security
[ 113]'.
1. Connect the PC to the 'Station'. Link [ 27]
2. Enable the 'Station'.
Press <MENU> and enter a valid PIN.
3. Update the firmware of the additional CPUs if there is a higher firmware version
status. Select the local connection as the connection type. Link [ 126]
4. Disconnect the PC from the 'Station'. Link [ 27]
See also
2 Loading configuration from the station to the PC [ 32]
22.3.2 Router station and Ethernet station
You can update the additional CPUs in a networked 'Station' via C-WEB/LAN. In
this way, you can update networked 'Stations' without disconnecting the network
connection and restoring the factory setting.
You will find additional information about the individual steps on the specified
pages.
w You are familiar with the information in chapter 'Preparation and security
[ 113]'.
w A GAP with DHCP is configured for the connection with the PC via C-
WEB/LAN.
1. Load the configuration from the 'Station' or your archive to the PC. Link [ 32]
2. Via the Ethernet switch (MM) FN2008-A1, connect the PC to the C-WEB/LAN.
3. Enable the 'Station'.
Press <MENU> and enter a valid PIN.
4. Update the firmware of the additional CPUs if there is a higher firmware version
status. Select the connection via GAP and enter the address of the 'Station'
you want to update. Link [ 126]
5. Load the configuration from the PC to the 'Station'. Link [ 30]
6. Disconnect the PC from C-WEB/LAN.