Updating the firmware
Converting the configuration
22
128 | 178
Building Technologies
A6V10210416_j_en_
--
Fire Safety
2018
-
-
29
22.4.2 Router station and Ethernet station
You will find additional information about t
he individual steps on the specified
pages.
w Familiarize yourself with the information in 'Preparation and security [ 113]'.
1. Import the new BDV into Cerberus-Engineering-Tool.
Select the 'File' > 'Import new BDV' menu item and open the file you want.
2. Load the configuration from the 'Station' or your archive to the PC. Link [ 32]
3. Convert the configuration and rectify conversion faults. Link [ 128]
4. Remove the network connection to the 'Station' and connect the PC. Link
[ 27]
5. Enable the 'Station'.
Press <MENU> and enter a valid PIN.
6. Load the converted configuration from the PC to the 'Station'. Link [ 30]
7. Disconnect the PC from the 'Station'. Link [ 27]
8. Restore the network connection.
22.5 Converting the configuration
You will find detailed information on converting 'Sites' in document
A6V10260976. See chapter 'Applicable documents'.
Converting the configuration
w The 'Site' you want to convert is saved and loaded in Cerberus-Engineering-
Tool.
1. Select the 'Edit' > 'Convert site' menu item.
a The following window opens:
2. Select the BDV you want and click on 'Convert'.
a The 'Action confirmation' window opens.
3. Click on 'Yes'.
a The 'Site' is converted.

Table of Contents