Connectivity and communication with 'Station'
Connecting the PC to the station
4
27 |
Building Technologies
4.3 Connecting the PC to the station
For most commissioning, maintenance and repair work a PC with installed
Cerberus-Engineering-Tool is required. The figure below shows the connection
between the PC and ↑ 'Station'.
Figure 1: Rear panel of operating unit and PC
LAN Ethernet connection
1 Required cable type: CAT 5, CAT 6, or CAT 7
4.4 Disconnecting the PC from the station
As the IP address is bound to the MAC address while there is a connection
between the PC and the 'Station' and as it remains in the cache even in the case of
a short break in the connection of ≤2 min., you must observe the following
instructions.
NOTICE
Establishing a connection to other 'Station' is not possible
Disconnect the PC from the '
' as described in the following instructions.
The connection between the PC and the 'Station' must be disconnected as follows:
1. Select 'Commissioning' > 'Disconnect' in Cerberus-Engineering-Tool.
2. Disconnect the cable connection between PC and 'Station'.
3. Wait ≥2 min. before you establish a connection to another 'Station'.
LAN
1