Commissioning Ethernet switch (MM) FN2008
Carrying out final commissioning work
16
87 |
Building Technologies
16 Commissioning Ethernet switch (MM)
FN2008-A1
This description focuses on correctly integrating the 'Ethernet switch (MM)
FN2008-A1' in the fire detection installation. More information about the product
can be found on the data carrier in the scope of supply and at the following
address: http://support.automation.siemens.com (Manufacturer designation:
Scalance X204-2)
NOTICE
No compliance with EN 54
● For an EN-54-compliant fire detection installation, you must use the permitted
Ethernet switch (MM) FN2008
Ethernet switch (MM) FN2008
' is a class A equipment and may cause
radio interference in residential areas. If interference does occur, observe the
relevant information in document A6V10210390. See chapter 'Applicable
documents'.
Commissioning
1. Install the 'Primary Setup Tool' software. Link [➙ 88]
2. Assign the IP address. Link [➙ 88]
3. Configure the FN2008-A1 using the Internet browser. Link [➙ 89]
4. In Cerberus-Engineering-Tool, create the ↑ links you want e.g., for the
following monitoring functions in a 'Technical zone'.
– Redundant power
– Display error contact
You will find detailed instructions on creating a
See chapter 'Applicable documents'.
A1 has no IP address in the factory setting. You must manually
assign the IP address.