Commissioning a control panel with integrated extinguishing
CE marking
14
73 |
178
Building Technologies
A6V10210416_j_en_
--
Fire Safety
2018
-
-
29
14.3 CE marking
Following the successful acceptance of the integrated extinguishing system, the
template for the extinguishing system's CE marking must be filled out. You will find
the form for printing out and completing in document 'A6V11370445'.
On the form, cross the applicable features of the extinguishing system and enter
the corresponding times. The following table shows an example for the CE
marking:
XXXX
Siemens Switzerland Ltd, Building Technologies
Gubelstrasse 22
6300 Zug, Switzerland
18
XXXX-XXX-XXXXX
EN 12094-1, electrical automatic control and time delay devices
Class of the ambient conditions: A
Flooding zone 1 Comment
High pressure gas
Pre-controlled sprinkler system
Delay of the triggering signal (4.17) 0 to 60 s
Signal representing the flow of the extinguishing agent (4.18) Pressure switch
Monitoring of the state/position of components (4.19)
Stop key (4.20)
Control of the discharge time (4.21) Sec. / minutes
Manual-only mode (4.23)
Triggering signals to equipment within the fire extinguishing
installation (4.24)
Extinguishing signals to spare cylinders (4.25)
Triggering of equipment outside the fire extinguishing installation
(4.26)
Emergency abort device (4.27)
Control of extended discharge (4.28)
Release of the extinguishing agent for selected flooding zones (4.29)
Activation of alarm devices with different alarm signals (4.30)
Response time for the activation state 3 s
Response time for activation of the outputs 1 s