net switch (modular) FN2012
A1 integrated into station
17
92 | 178
17.2 FN2012-A1 integrated into station
This description is for an FN2012-A1 that is connected to the station via a ribbon
cable.
You will find information on mounting and
A6V10210390. See chapter 'Applicable documents'.
A1 has no IP address in the factory setting.
You will find an overview on converting a configuration in chapter '
configuration [➙ 128]'.
You will find detailed information on converting a site to the latest market package
in document 'A6V10260976'. See chapter 'Applicable documents'
Commissioning an integrated FN2012-A1
w The FN2012-A1 is connected to the station via a ribbon cable.
w The rotary switch on the FN2012-A1 is set to '0'.
l Configure the integrated Ethernet switch FN2012-A1 in the Engineering Tool.
You will find detailed information on configuring the Ethernet switch FN2012-A1
in document A6V10210424. See chapter 'Applicable documents'.
See also
2 Commissioning a web interface [➙ 93]
2 Converting the configuration [➙ 128]