Commissioning Ethernet switch (modular) FN2012
-
A1
Standalone FN2012
-
A1
17
91 |
178
Building Technologies
A6V10210416_j_en_
--
Fire Safety
2018
-
-
29
Rotary switch for device configuration
An Ethernet switch that is not integrated in a station must be configured via the
rotary switch. If the Ethernet switch is integrated, the rotary switch must be set to
'0'.
Using the rotary switch for device configuration, the Ethernet switch can be set to
pre-defined network addresses or operation modes.
To apply a new configuration, the setting must be made when the device is de-
energized or by means of a hardware reset.
Switch position IP address / operation mode Sub-net mask / operation mode
0
Configured via web interface or MoNet
bus
Factory setting: 0.0.0.0
Configured via web interface or MoNet
bus
Factory setting: 255.255.248.0
1 192.168.99.241 255.255.248.0
2 192.168.99.242 255.255.248.0
3 192.168.99.243 255.255.248.0
4 192.168.99.244 255.255.248.0
5 192.168.99.245 255.255.248.0
6 192.168.99.246 255.255.248.0
7 192.168.99.247 255.255.248.0
8 192.168.99.248 255.255.248.0
9 192.168.99.249 255.255.248.0
A 192.168.99.250 255.255.248.0
B 192.168.99.251 255.255.248.0
C 192.168.99.252 255.255.248.0
D Reserved (0.0.0.0) Reserved (255.255.255.255)
E Repeater operation Repeater operation
F 192.168.200.4 255.255.255.0