Restoring factory setting on the 'Station'
24
163 |
178
Building Technologies
A6V10210416_j_en_
--
Fire Safety
2018
-
-
29
24.11 Restoring factory setting on the 'Station'
There are the following ways in which to restore the factory setting on the
'Station':
Via the menu on the display
With the 'S32' button
Via the menu on the display
1. Press <MENU>.
a You are prompted to enter a PIN.
2. Enter a valid PIN and confirm with <ok>.
a The 'User successfully logged in' message is displayed.
a The main menu is displayed.
3. Select the 'Topology' > 'Hardware tree' > 'Station' menu items.
4. Press the 'More Options' softkey and select 'Execute commands'.
5. NOTICE! Configuration will be deleted! Save the configuration data for the
'Station' before restoring the factory setting.
6. WARNING! It is impossible to acquire and process alarms or faults without a
site configuration! Select the 'Factory reset' command.
a The 'Station' restarts.
7. Enter the date and time. To do this, select the 'Settings/administration' >
'System commands' > 'Set system time' menu items.
PMI & mainboard FCM2004
1. NOTICE! Configuration will be deleted! Save the configuration data for the
'Station' before restoring the factory setting.
2. Set the 'S38-1' switch to 'ON' on the rear of the operating unit.
3. WARNING! It is impossible to acquire and process alarms or faults without a
site configuration! Press the 'S32' button for >2 s until the 'Station' restarts.
a The 'Station' restarts.
4. Set the 'S38-1' switch to 'OFF' after the restart.
5. Enter the date and time. To do this, select the 'Settings/administration' >
'System commands' > 'Set system time' menu items.