Commissioning Ethernet switch (modular) FN2012
-
A1
Standalone FN2012
-
A1
17
90 | 178
Building Technologies
A6V10210416_j_en_
--
Fire Safety
2018
-
-
29
17 Commissioning Ethernet switch (modular)
FN2012-A1
Malfunctions
during a partial upgrade
Ethernet switch (modular) FN2012 is not compatible with Ethernet switch (MM)
FN2008 and so may only be used in panels MP6.
See also
2 Updating the FW of Ethernet switch (modular) FN2012-A1
[ 142]
17.1 Standalone FN2012-A1
This description is for a standalone FN2012-A1 that is not connected to the station.
You will find information on mounting and installing the FN2012
-
A1 in document
A6V10210390. See chapter 'Applicable documents'.
The FN2012
-
A1 has no IP address in the factory setting.
Commissioning the standalone FN2012-A1
w The FN2012-A1 is not connected to the station.
1. Use the rotary switch to define a pre-configured IP address. Link [ 90]
2. Put the web interface into operation. Link [ 93]
3. Change the IP address of the FN2012-A1 in accordance with your network
requirements. Link [ 94]
4. Configure the redundancy role of the FN2012-A1. Link [ 95]
5. Deactivate any local ports on the FN2012-A1 that are not being used in
accordance with your safety requirements. Link [ 95]
6. Configure fault monitoring for local ports. Link [ 96]
17.1.1 Specifying a pre-configured IP address
You must assign a pre-configured IP address to a standalone FN2012-A1 as part
of its commissioning process.
1. Use the rotary switch on the FN2012-A1 to select an IP address in accordance
with the table further below.
2. Wait 10 s or reset the FN2012-A1 using the RESET button in order to apply the
set IP address.
If the rotary switch of the FN2012
-
A1 is in position 'E', the local ports are not
available. You cannot perform a firmware update or call up a web interface for the
FN2012-A1 when the switch is in position 'E'.