Detailed commissioning steps
Delete the device on Person Machine Interface
15
83 |
Building Technologies
15.15 Delete the device on Person Machine Interface
1. Mark the corresponding device fault message.
2. Press the 'More Options' ↑ softkey.
3. Select the 'Show topology' menu item.
a The ↑ logical channel is displayed. For some devices, 'Device' is displayed
directly.
4. Press the 'More Options' softkey.
5. Select the 'Jump to link' menu item.
a The ↑ physical channel is displayed.
6. Press the 'Upper level' softkey.
a 'Device' is displayed.
7. Press the 'More Options' softkey.
8. Select the 'Execute commands' menu item.
9. Select the 'Remove/delete device' command.
a The control panel deletes the physical representation of the removed device.
a The logical channel element remains in the 'Zone'.
15.16 Remove the elements
If you have uninstalled an C-NET device for good, the corresponding elements,
e.g. the 'Cerberus-Engineering-Tool' must be removed from the logical structure
trees in Zone. You can search for elements using the 'Find' function.
You will find more information in document A6V10210424. See chapter 'Applicable
documents'.
See also
2 Applicable documents [➙ 11]
15.17 Testing detectors
The commissioning personnel perform the function test for the ↑ automatic fire
detectors and the 'Manual call points'.
You will find additional information about the individual steps on the specified
pages.
w The ↑ detector line has been commissioned.
1. Switch the test mode on. Link [➙ 84]
2. Initiate the detector. Link [➙ 84]
3. Switch ↑ normal operation on. Link [➙ 85]
4. Test the logged test activations. Link [➙ 84]