Changing and expanding the FDnet/C
-
NET detector line
Replacing 'Manual call point' of the same type
12
55 |
178
Building Technologies
A6V10210416_j_en_
--
Fire Safety
2018
-
-
29
12.5 Replacing 'Manual call point' of the same type
NOTICE
Incorrect assignment between detector/detector zone and customer text
Inaccurate messages in the event of an alarm
You must not change the C-NET topology at the same time as adding extra
devices.
After extending or changing a 'Site' always run a test to check the
assignment between detector/detector zone and customer text.
You will
find additional information about the individual steps on the specified
pages.
1. Switch on the replace mode. Link [ 55]
2. Replace the 'Manual call point' with a 'Manual call point' of the same type.
3. Switch off the replace mode. Link [ 56]
4. Test the 'Manual call point'. Link [ 56]
5. Switch normal operation on. Link [ 85]
6. Connect the PC to the 'Station'. Link [ 27]
7. Load the configuration from the 'Station' to the PC. Link [ 32]
8. Test the function of the 'Site'. Link [ 86]
9. Remedy any errors you notice and load the corrected configuration from the
PC to the 'Station'. Link [ 30]
10. Disconnect the PC from the 'Station'. Link [ 27]
You will find more information about installing and uninstalling in the
documentation for the corresponding 'Manual call point'.
12.5.1 Switching on the replace mode
1. Select 'Functions' > 'All functions' > 'Detector' in the main menu.
2. In the 'Zone', enter the 'Zone' address and press <ok>.
3. Enter the detector address in 'Detect.' and press <ok>.
4. Select the 'Device replace mode ON' menu item.
a The following message is shown following successful switching on: 'Command
executed'.
a The yellow 'ISOLATION' LED lights up.
a The detector line is de-energized.