Repair
Correcting swapped devices
24
158 | 178
Building Technologies
A6V10210416_j_en_
--
Fire Safety
2018
-
-
29
24.6 Correcting swapped devices
When non-stationary C-NET devices have been swapped over in their bases, e.g.,
while work is carried out, the 'Line' is not fault-free.
The following message is shown on the display of the Person Machine Interface
for each C-NET device that has been swapped over:
'Zone', 'Serial no. ("ID-Nr.")', 'Device missing'
If the C-NET detector line was restarted, the following message is displayed for
each swapped C-NET device:
'Zone', 'Serial no. ("ID-Nr.")', 'Dev.location fault'
Troubleshooting
'
Faults
' of
C
-
NET
devices of the same type that have been swapped over can
then be rectified using the Person Machine Interface without having to find the
original base.
w The device types in the corresponding bases are correct.
1. Rectify localization errors. Link [ 86]
2. Connect the PC to the 'Station'. Link [ 27]
3. Load the configuration from the 'Station' to the PC.
4. Disconnect the PC from the 'Station'. Link [ 27]