Commissioning overview
Commissioning variants
5
34 | 178
Building Technologies
A6V10210416_j_en_
--
Fire Safety
2018
-
-
29
5 Commissioning overview
The 'Stations' on the C-WEB, such as control panels FC722/FC724 and fire
terminals FT724, are connected to the power supply and commissioned by the
installation and commissioning personnel.
Networked 'Stations' must only be commissioned with Cerberus-Engineering-
Tool.
Standalone control panels can be commissioned with or without Cerberus-
Engineering-Tool.
NOTICE
Impermissible commissioning procedures result in faults during operation.
Only the procedures described in this document are permitted.
5.1 Commissioning variants
NOTICE
Not the current firmware version status of a newly installed fire detection
installation
Possible limitations for the configuration or use of devices.
Compare the firmware version of a newly installed fire detection installation
with the currently approved firmware version status.
Use the currently approved firmware version status.
Update the firmware if required, in accordance with the chapter 'FW update
for main CPU and additional CPUs' in document A6V10210416; see chapter
'Applicable documents'.
The table below provides an overview of the procedure for commissioning the
'Stations'. The letters A, B1, B2 and C refer to the detailed descriptions in the
following chapters.
Standalone control panel Networked 'Stations'
Without
Cerberus-
Engineering-
Tool
No pre-
configuration
possible
A
Auto-configuration
Adaptations on the Person
Machine Interface
Not possible.
With
Cerberus-
Engineering-
Tool
Without pre-
configuration
B1
Auto-configuration
Adaptations in Cerberus-
Engineering-Tool
C
Initialize the 'Stations' for
networking
Read in the C-NET devices by line
Assign the logical elements to
Cerberus-Engineering-Tool
With pre-
configuration
B2
Read in the FDnet devices by line
Assign the logical elements to
Cerberus-Engineering-Tool
Table 1: Commissioning variants