5 Commissioning overview
The 'Stations' on the C-WEB, such as control panels FC722/FC724 and fire
terminals FT724, are connected to the power supply and commissioned by the
installation and commissioning personnel.
● Networked 'Stations' must only be commissioned with Cerberus-Engineering-
Tool.
● Standalone control panels can be commissioned with or without Cerberus-
Engineering-Tool.
NOTICE
Impermissible commissioning procedures result in faults during operation.
Only the procedures described in this document are permitted.
5.1 Commissioning variants
NOTICE
Not the current firmware version status of a newly installed fire detection
installation
Possible limitations for the configuration or use of devices.
● Compare the firmware version of a newly installed fire detection installation
with the currently approved firmware version status.
● Use the currently approved firmware version status.
● Update the firmware if required, in accordance with the chapter 'FW update
for main CPU and additional CPUs' in document A6V10210416; see chapter
The table below provides an overview of the procedure for commissioning the
'Stations'. The letters A, B1, B2 and C refer to the detailed descriptions in the
following chapters.
Standalone control panel Networked 'Stations'
Without
Cerberus-
Engineering-
Tool
No pre-
configuration
possible
A
● ↑ Auto-configuration
● Adaptations on the ↑ Person
Machine Interface
Not possible.
With
Cerberus-
Engineering-
Tool
Without pre-
configuration
B1
● Auto-configuration
● Adaptations in Cerberus-
Engineering-Tool
C
● Initialize the 'Stations' for
networking
● Read in the C-NET devices by line
● Assign the logical elements to
Cerberus-Engineering-Tool
With pre-
configuration
B2
● Read in the FDnet devices by line
● Assign the logical elements to
Cerberus-Engineering-Tool
Table 1: Commissioning variants