Updating the firmware
Updating the FW of the peripheral devices
22
136 | 178
Building Technologies
A6V10210416_j_en_
--
Fire Safety
2018
-
-
29
22.8.4 Mimic display driver FT2001-A1
WARNING
Incorrect assignment between detector/detector zone and
customer text
Misleading messages in the event of an alarm
Never change the wiring during the firmware update.
The firmware must be updated individually for each mimic display driver.
Preparation
w The mimic display driver is fed by a 24 V external power supply or by the C-
NET detector line.
w The driver for the MCL-USB adapter FDUZ221 or FDUZ227 is installed on the
PC.
1. Select 'File' > 'Import new resource package'.
2. In the selection window, open an F-FXS7211-XX_x_x_...zip file matching the
'Site'.
3. Connect the PC to the device via the MCL-USB adapter.
Figure 6: Connection of the PC to the mimic display driver
FDUZ221 /
FDUZ227
MCL-USB adapter (interface USB/MC-LINK)
X2 Connection for the MCL-USB adapter
FT2010 Mimic display driver
FT2001-A1
X2
MC-Link
FDUZ221/FDUZ227
USB