Commissioning standalone 'Station' with PC, with pre
8
42 | 178
8 B2 - Commissioning standalone 'Station' with
PC, with pre-configuration
The procedure in this chapter is only valid for
In this commissioning variant, in Cerberus-Engineering-Tool, first manually
configure a ↑ 'Site' up to 'Line' level. Then read in the C-NET devices and adapt
the configuration manually in Cerberus-Engineering-Tool.
Prerequisites
● The ↑ detector lines and C-NET devices are installed.
● The acceptance test has been carried out for the detector lines.
● The ↑ 'Station' is installed, but the batteries are not connected yet.
● The cables for the detector lines and the mains supply have been inserted in
the 'Station', but not yet connected.
● Cerberus-Engineering-Tool is installed on the PC.
● The current firmware and ↑ BDV are available on the PC.
You will find additional information about the individual steps on the specified
pages.
Commissioning
1. In Cerberus-Engineering-Tool create a 'Site' and configure it manually to the
'Zone' level.
2. Prepare the 'Station' for commissioning – without BDV installation. Link [➙ 75]
3. Connect the PC to the 'Station'. Link [➙ 27]
4. Load the configuration from the PC to the 'Station'. Link [➙ 30]
5. Read-in the C-NET devices. Link [➙ 82]
6. Load the configuration from the 'Station' to the PC. Link [➙ 32]
7. Adapt the configuration in Cerberus-Engineering-Tool. Link [➙ 77]
8. Load the configuration from the PC to the 'Station'. Link [➙ 30]
9. Test the function of the 'Site'. Link [➙ 86]
10. Remedy any errors you notice and load the corrected configuration from the
PC to the 'Station'. Link [➙ 30]
11. Disconnect the PC from the 'Station'. Link [➙ 27]
12. Perform the completion tasks. Link [➙ 86]