dating the FW of the additional CPUs only
22
126 | 178
22.3.3 FW update for additional CPUs
NOTICE
Updating the firmware of the degraded mode module FN2001
If the firmware of the degraded mode module FN2001 has to be updated, it must
be temporarily connected to the slot for the main module FN2001 (from slot X12
to X13).
w You are familiar with the information in chapter 'Preparation and security'.
1. Select 'Update' > 'FW update additional CPUs' from the menu bar.
2. If the 'Password check' window opens, enter the password '12345678' and click
on 'OK'.
a The 'Connect' window opens.
3. Select the connection type:
– Select 'Local connection' to establish a connection to the connected
↑ standalone or ↑ SAFEDLINK 'Station'.
– Select 'Connection to GAP' to establish a connection via ↑ GAP to a
networked 'Station'. Enter the address of the 'Station' you want to update in
the 'Target station address' field. If you want to update the GAP 'Station'
itself, enter '0'.
4. Click on 'OK'.
a The 'FW update additional CPUs' window opens.
a The checkboxes for the CPUs that can be updated are checked in column
'Update'.
5. Select the CPUs you want to update and click on 'Start'.
a The 'Set access level' window opens.
6. Press <MENU> on the 'Station' and enter a valid PIN.
7. Click on 'OK' in the 'Set access level' window.
a The CPUs are updated.
a The 'Information' window is opened after updating.
8. Note the update information and information about other procedures in the
'Information' window.
9. Click on 'OK'.
a The 'Station' is restarted.
a After a few minutes, the 'Buzzer' sounds twice.