Commissioning Ethernet switch (MM) FN2008
Install Primary Setup Tool
16
88 | 178
16.1 Install Primary Setup Tool
The 'Primary Setup Tool' software is
included in the scope of supply for the
FN2008-A1.
l Start 'Primary Setup Tool' installation.
a Primary Setup Tool is installed.
a The DLC and PROFINET RT protocols are installed.
a Primary Setup Tool recognizes one or more connected FN2008-A1 without IP
address via the DLC protocol.
16.2 Assign IP address
w Primary Setup Tool is installed on the PC.
w Several FN2008-A1 are physically linked in the system.
1. Connect the PC to any available FN2008-A1 port P1…P4 using a network
cable.
2. Start the Primary Setup Tool via 'Start' > 'Programs' > 'Simatic'.
a Primary Setup Tool lists one or more FN2008-A1 (X204-2).
3. Select each FN2008-A1 one after the other and issue a unique IP address
(192.168.1.xxx) to each FN2008-A1.
4. Click on the connected FN2008-A1 in the tree view and select the 'Load' menu
item.
a The assigned IP address is saved to the FN2008-A1.
5. Repeat the 'Load' process for each FN2008-A1.
a Each FN2008-A1 in the system has an individual IP address.