Repair
Fault messages on the Person Machine Interface
24
156 | 178
Building Technologies
A6V10210416_j_en_
--
Fire Safety
2018
-
-
29
24.3 Fault messages on the Person Machine Interface
Figure 9: Fault messages on the Person Machine Interface
The table below shows the causes and measures should a fault be displayed.
LED LED flashes Cause What must be done
1 FAULT The 'Site' has a fault
Check whether another fault LED is
flashing, if not:
Check the display
Check whether the 'Fault' control
input is activated
5 Fault System Failure of the main CPU Visual check of the cable connections
Check whether the red LED H37 on the
operating unit FCM72xx is on:
Exchange PMI & mainboard
'Fault' of a component Restart 'Station'
When the 'Fault' is still indicated:
Exchange the module
Communication fault of a
networked 'Station'
Check the transmission line
Check the faulty 'Station'
8
Fault / Off Remote
alarm
Remote transmission has a
'Fault'
Check remote transmission
10
Fault / Off Alarm
device
'Fault' affecting acoustic
control lines
Check the 'Line' for open circuit/short-
circuit or end-of-line element (EOL) is
missing or defective
12
Fault / Off Control
function
'Fault' affecting fire control
lines
Check the 'Line' for open line/short-circuit
Check the function of the external control
devices
Check the function, any existing
feedback switch
12
10
8
5
1