Repair
Restoring factory setting on the 'Station'
24
164 | 178
Building Technologies
A6V10210416_j_en_
--
Fire Safety
2018
-
-
29
PMI & mainboard FCM2027
1. NOTICE! Configuration will be deleted! Save the configuration data for the
'Station' before restoring the factory setting.
2. WARNING! It is impossible to acquire and process alarms or faults without a
site configuration! Keep the 'S32' button on the rear of the operating unit
pressed and simultaneously press <Reset> on the Person Machine Interface
until the 'Station' restarts (>2 s).
a The Station restarts.
3. Enter the date and time. To do this, select the 'Settings/administration' >
'System commands' > 'Set system time' menu items.