Connectivity and communication with 'Station'
Loading configuration from the PC to the station
4
31 |
Building Technologies
WARNING
Activation of fire or smoke dampers
If fire or smoke dampers are connected to the FS720 via an input/output module,
they may be activated when the station is switched off or when the station or
detector line is restarted.
● If necessary, block the outputs temporarily [➙ 81] before switching off the
station or restarting the station/detector line.
w The ↑ 'Site' is opened in Cerberus-Engineering-Tool.
w The PC is connected to the 'Station'.
w Networked 'Stations' are initialized.
w 'Station' and Cerberus-Engineering-Tool have the same 'Site' ID.
w 'Station' and Cerberus-Engineering-Tool are part of the same sales channel.
1. Select 'Commissioning' > 'Download site' in Cerberus-Engineering-Tool.
a The 'Download site' and 'Connect' windows open in Cerberus-Engineering-
Tool.
2. Select the connection in the 'Connect' window and click on 'OK'.
a The 'Stations' are listed in the 'Download site' window.
3. Select the 'Stations' whose configuration you would like to load from 'Cerberus-
Engineering-Tool' to the 'Stations' and click on 'Start'.
a The 'Set access level' window may open in Cerberus-Engineering-Tool with
the 'Set the station to access level 3' prompt. Press <MENU> on the
'Station', enter the PIN and press <ok>.
4. Click on 'OK' in the 'Set access level' window in Cerberus-Engineering-Tool.
a The 'Action confirmation' window opens in Cerberus-Engineering-Tool.
5. Click on 'Yes'.
a The configuration is loaded to the 'Station'.
a The progress is displayed in the 'Download site' window in Cerberus-
Engineering-Tool.
a The 'Station' restarts.
a After a few minutes, the 'Buzzer' sounds twice at the 'Station'.
6. Press <Acknowledge> on the ↑ Person Machine Interface at the 'Station' to
switch off the 'Buzzer'. Do not perform any more actions on the 'Station' until
the 'Buzzer' has sounded for the second time.
See also
2 Loading data to the 'Station' [➙ 28]