Building Technologies Division Basic Documentation LME7... CC1P7105en
Infrastructure & Cities Sector 18 PME73.831… 29.11.2011
Value range Parameter
number
Parameter Edit
Min. Max.
Resolution Factory setting Password level
reading from level
Password level
writing from level
200
Burner control
224
Specified time air pressure switch Edit
0 s 13.818 s 0.294 s 12.054 s SO OEM
225
Prepurge time -2,1 seconds Edit
0 s 1237 s 4.851 s 29.106 s SO OEM
226
Preignition time Edit
1.029 s 37.485 s 0.147 s 2.058 s SO OEM
230
Interval: End of ignition safety time – fuel valve 1 ON Edit
3.234 s 74.97 s 0.294 s 3.234 s SO OEM
231
Interval: Fuel valve 1 ON – pilot valve OFF Edit
0 s 74.97 s 0.294 s 2.940 s SO OEM
232
Interval: Pilot valve OFF – release of load controller Edit
2.058 s 74.97 s 0.294 s 8.820 s SO OEM
234
Postpurge time Edit
0 s 1237 s 4.851 s 0 s SO OEM
239 Intermittent operation after 24 hours of continuous operation
0 = OFF
1 = ON
Edit 0 1 1 1 SO OEM
240
Repetition in the event of loss of flame during operation
0 = none
1 = none
2 = 1 x Repetition
Edit
0 2 1 0 SO OEM
241.00
Valve proving
0 = OFF
1 = ON
Edit
0 1 1 1 SO OEM
241.01
Valve proving
0 = during prepurge time
1 = during postpurge time
Edit
0 1 1 0 SO OEM
241.02
Valve proving
0 = according to P241.01
1 = during prepurge time and postpurge time
Edit
0 1 1 0 SO OEM
242
Valve proving test space evacuating Edit
0 s 2.648 s 0.147 s 2.648 s SO OEM
243
Valve proving time test atmospheric pressure Edit
1.029 s 37.485 s 0.147 s 10.290 s SO OEM
244
Valve proving test space filling Edit
0 s 2.648 s 0.147 s 2.648 s SO OEM
245
Valve proving time test gas pressure Edit
1.029 s 37.485 s 0.147 s 10.290 s SO OEM
247 Dauerpilot (während Betrieb)
0 = Aus
1 = Ein
einstellbar 0 1 1 0 HF OEM
254 Response time detector error
0 = 1 s
1 = 3 s
Edit 0 1 1 0 SO OEM
257
Postignition time -0.3 seconds Edit
0 s 13.23 s 0.47 s 2.205 s SO OEM

Table of Contents

Other manuals for Siemens LME7 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens LME7 Series and is the answer not in the manual?

Siemens LME7 Series Specifications

General IconGeneral
BrandSiemens
ModelLME7 Series
CategoryController
LanguageEnglish

Related product manuals