Communications
11.5 Modbus RTU/ASCII Protocol
BW500 and BW500/L
136 Operating Instructions, 12/2016, A5E33482052-AD
Type
Description
Start
# R
Parameter
Values
Read
Reference
DD 41,002 1 1 - 31 r/w
Time
(R41,000
41,006)
section
given below
and also
P008
(Page 154)
hh
41,003
1
00 - 23
r/w
Refer to the
Date and
Time
(R41,000
41,006)
section
given below
and also
P009
(Page 155)
mm
41,004
1
00 - 59
r/w
ss 41,005 1 00 - 59 r/w
Time Zone 41,006 1 -12 - 12 r/w see P739
(Page 186)
Process
Values
Rate
41,010
2
32 bits
r
Refer to the
Process
Values
(R41,010
R41,048)
section
given below.
Load
41,012
32 bits
r
Speed
41,014
2
32 bits
r
Total 1
41,016
2
32 bits
r
Total 2 41,018 2 32 bits r
Device State 41,020 1 bit mapped r Refer to
the
Process
Values
(R41,010
R41,048)
section
given below.
Command
Control
41,022 1 bit mapped r/w Refer to
Command
Controls
(41,022)
given below.
Multi-Span
Selection
41,024 1 1 - 8 r/w Refer to
Multispan
(Page 81)
and P365
(Page 170).
Total 1 dec-
imal places
41,025 1 1 - 3 r/w Refer to
Read/Write
(R41,025
R41,026)
Total 2 dec-
imal places
41,026 1 1 - 3 r/w