Parameters
12.2 Relay/Alarm Function (P100 - P117)
BW500 and BW500/L
160 Operating Instructions, 12/2016, A5E33482052-AD
Sets the dead band for the relay selected; BW500: relays 1 to 5 (P100 -01 to -05); BW500/ L:
relays 1 and 2 (P100 -01 to -02). The dead band prevents relay chatter due to fluctuations at the
high or low setpoint (
f
= 3.0).
Enter the value in % of full scale, or for deviation alarm enter % of setpoint, range is 1 to 10 %.
Note
Not applicable if P100 = 4, 7, or 8.
Sets the logic applied to relays to determine their open or closed state.
The relays on the BW500 default to normally open under power loss.
In software, all relays are programmed the same way; with
setpoints always indicating relay
action. This parameter allows the reversal of the operation. Normally, P118 = 2 for each relay.
When P118 = 3, the operation of the indexed relay is reverse from normal.
f
This function allows the user to simulate an alarm condition: ON or OFF, which will override
normal operation until P119 setting is returned to normal.