Recalibration
7.4 Recalibration
BW500 and BW500/L
80 Operating Instructions, 12/2016, A5E33482052-AD
Span Calibration. Current Span
Setup test. Press ENTER to start
41900
For example: the current span count.
Note
End of span calibration. Remove the test weight and return to RUN
.
Direct span entry (P368) is intended for use when replacing software or hardware, and when it is
not convenient to perform an initial span. A record of the last valid span count is required.
Access P368 and enter EDIT mode
P368-01 Direct Span Entry
E
Press the following keys in a given sequence:
P368-01 Direct Span Entry
V
For example: the last valid span count.