Parameters
12.12 SmartLinx Hardware Testing
BW500 and BW500/L
188 Operating Instructions, 12/2016, A5E33482052-AD
The results of ongoing hardware tests in the communications circuitry.
FAIL least significant byte (LSB) is given firstError
occurred communicating with card; device will try
to reinitialize communications with card. If mes-
sage continues, record values in P791 and P792
and contact your local Siemens representative.
ERR1 No module installed, or module not supported;
SmartLinx communications have been disabled
If FAIL or ERR1 is displayed in P790 (Hardware Error), go to P791 (Hardware Error Code) and
P792 (Hardware Error Count) for information about the error.
Indicates the precise cause of
or
condition from P790.
Any other value Error code; provide this code to your Siemens
representative for troubleshooting
P792 Hardware Error Count
A count that increments by 1 each time Fail is reported in P790 (Hardware Error).
Range: 0 to 9999 Error count; provide this number to your Siemens
representative for troubleshooting.
P794 SmartLinx Module Type
This parameter is used to identify the module type when SmartLinx is used. If you are not using
SmartLinx, this parameter is not functional. Please see the associated SmartLinx instruction
manual for a full description of this parameter.