Communications
11.6 Modems
BW500 and BW500/L
148 Operating Instructions, 12/2016, A5E33482052-AD
Master
Modem
auto answer off (dip switch?)
load factory default (dip switch?)
no flow control (dip switch?)
baud rate = 9600
10 data bits (probably the default)
Modbus RTU Software
baud rate = 9600
8 bit
no parity
1 stop bit
dial prefix: ATDT
Initialization command: ATE0Q0V1X05=0512=100
Reset command: ATZ
Hang-up command: ATHO
Command response delay: 5 seconds
Answer Delay: 30 seconds
Inter-character delay: 55 ms
Slave
Modem
auto answer on (dip switch?)
load factory default (dip switch?)
no flow control (dip switch?)
baud rate = 9600
10 data bits (probably the default)