Byte Bit Data format Soft starter diagnostics Error types 3RW
F
5)
+ F
6)
50
1)
52
2)
55
3)
55-F
4)
11 1 Bool No main power 0x010A x r r r r
3 Bool Starting mode active - - r r r r
4 Bool Stopping mode active - - r r r r
6 Bool Electrical braking active - - - - r -
7 Bool Creep speed active - - - - r -
12 0 Bool Temperature sensor overload 0x1024 x r r r r
1 Bool Temperature sensor wire break 0x1026 x r r r r
2 Bool Temperature sensor short-circuit 0x1025 x r r r r
3 Bool Thermal motor model overload 0x1022 x r r r r
4 Bool Motor overload protection - shuto󹪜 0x1046 - r r r r
5 Bool Idle time active - - - - r r
6 Bool Cooling time active - - r r r r
7 Bool Safety-related shuto󹪜 0x0019 x - - - r
13 3 Bool Current limiting active - - r r r r
6 Bool Generator operation 0x1011 - - - r r
7 Bool Input control - - r r r r
14 0 Bool Asymmetry limit error exceeded 0x1021 - - - r r
1 Bool Asymmetry shuto󹪜 0x1046 - - - r r
2 Bool Current limit error exceeded 0x1040 - - - r r
3 Bool Current limit error undershot 0x1041 - - - r r
4 Bool Current limit error shuto󹪜 0x1046 - - - r r
15 0 Bool Input 1 - - r r r r
1 Bool Input 2 - - - - r r
2 Bool Input 3 - - - - r r
3 Bool Input 4 - - - - r r
16 0 Bool Ground fault limit error exceeded 0x1027 - - - r r
2 Bool Quick-stop active - - - - r r
6 Bool Maximum pointer reset - - r r
7)
r r
7 Bool Electronics supply voltage too low 0x1084 x r r r r
17 0 Bool Bus error - - r r r r
1 Bool CPU/Master STOP - - r r r r
2 Bool Automatic mode - - r r r r
3 Bool Operating mode manual - - r r r r
4 Bool Operating mode manual - local - - r r r r
6 Bool Connection abort in manual mode 0x1098 - r r r r
7 Bool Error process image 0x1096 x - - r r
18 0 Bool Parameter assignment active - - - - r r
1 Bool Invalid parameter value 0x1095 x - - r r
2 Bool Parameters cannot be changed in ON state - - - - r r
3 Bool Parameters disable CPU/master active - - - - r r
4 Bool No external start parameters received 0x1033 - - - r r
Appendix
A.4 Data sets
SIRIUS 3RW5 PROFINET communication modules
Equipment Manual, 05/2021, A5E35631297002A/RS-AD/004 169