Object
No.
Byte Bit Data format Parameters Value range
[encoding]
Incre‐
ment
3RW
50 / 52
1)
[D
3)
]
55 /
55‑F
2)
[D
3)
]
5 18 0 Bit2 Response to overload
thermal motor model
9)
[0 ... 1] - r
[0]
r/w
4)
[0]
[0] Turn o without restart
[1] Turn o with restart
232 4 Bit4 Response to faulty main
power
9)
[1 ... 2] - - r/w
[1]
[1] Group error only at ON
command
[2] Warn
6 19 0 Bit4 Tripping class [0 ... 15] - r
50: [0]
52: [3]
r/w
4)
[0]
[0] CLASS 10E
[1] CLASS 20E
[2] CLASS 30E
5), 6)
[3] CLASS 10A
[15] CLASS OFF
7 20 0 Unsigned8 Recovery time
9)
60 … 1 800 s
[2 … 60]
30 s - r/w
4)
[10]
10 24 0 Bit2 Response to overload
temperature sensor
9)
[0 ... 2] - r
[0]
r/w
4)
[0]
[0] Turn o without restart
[1] Turn o with restart
[2] Warn
5), 6)
9 2 Bit4 Temperature sensor
9)
[0 ... 2] - - r/w
4)
[0]
[0] Deactivated
[1] Thermoclick
[2] PTC type A
140 33 2 Bit2 Response to overload
switching element
9)
[0 ... 1] - r
[0]
r/w
[0]
[0] Turn o without restart
[1] Turn o with restart
21 34 0 Bit4 Asymmetry limit error
9)
10 … 60 %
[2 … 12]
5 % - r/w
[6]
[0] Deactivated
47 45 0 Unsigned8 DC braking torque 20 … 100 %
[4 … 20]
5 % - r/w
8)
[10]
40 48 0 Unsigned8 Starting voltage 20 … 100 %
[4 … 20]
5 % r
[6]
r/w
[6]
Appendix
A.4 Data sets
SIRIUS 3RW5 PROFINET communication modules
182 Equipment Manual, 05/2021, A5E35631297002A/RS-AD/004