Error type Inter‐
rupt
type
Error / Warning Cause + F
1)
Byte.Bit
2)
0x1021 ER Asymmetry A limit value for asymmetry has been exceeded.
Asymmetry can cause an overload.
• Phase failure.
• Fault in the motor windings.
- 14.0
0x1021 MT - 62.6
0x1022 ER Therm. motor model over‐
load
• The motor feeder has been overloaded.
• The motor temperature rise has exceeded a lim‐
it.
x 12.3
0x1022 MT - 62.3
0x1024 ER Temperature sensor over‐
load
The temperature of the motor is too high. x 12.0
0x1024 MT - 22.5
0x1025 ER Temperature sensor short
circuit
A short circuit has occurred in the temperature sen‐
sor cable.
x 12.2
0x1025 MT - 22.7
0x1026 ER Temperature sensor wire
break
A wire has broken in the sensor cable of the tem‐
perature sensor.
x 12.1
0x1026 MT - 22.6
0x1027 ER Ground fault The ground-fault monitoring has responded. An
impermissibly high residual current is owing.
- 16.0
0x1027 MT - 62.7
0x1033 ER No start-up data received Data necessary for device start-up are missing. - 18.4
0x1034 MT Starting time exceeded The set maximum starting time is shorter than the
starting time required by the motor.
- 92.2
0x1035 MT Starting time undershot The set minimum starting time is longer than the
starting time required by the motor.
- 92.3
0x1036 MT Parameters for Ex motor pro‐
tection received
4)
Parameters for the EX motor protection have been
received.
- 60.2
0x1040 ER Threshold I exceeded The current has exceeded a limit. - 14.2
0x1040 MT - 62.4
0x1041 ER Threshold I undershot The current has undershot a limit. - 14.3
0x1041 MT - 62.5
0x1042 MT Threshold P exceeded The active power of the motor has exceeded a limit
value.
- 83.2
0x1042 ER - 83.4
0x1043 MT Threshold P undershot The active power of the motor has undershot a limit
value.
- 83.3
0x1043 ER - 83.5
0x1046 ER Actuator disconnection The module has disconnected the actuator. An ad‐
ditional diagnostic message will be displayed to
provide you with more detailed information about
the cause.
- 12.4
14.1
14.4
83.6
0x1057 ER Number of switch-on opera‐
tions exceeded
The permissible number of switch-on operations in
the monitoring period has been exceeded.
x 71.1
0x1057 MT - 71.3
0x1080 ER Device error Irrecoverable error detected following self-diagnos‐
tics (self-test, contactor contacts, switching ele‐
ment, etc.).
- 19.2
0x1081 ER Bypass defective
• Bypass defective
• The error can also be generated by successive,
brief interruptions of the control supply voltage.
x 29.3
Messages and diagnostics
7.2 Diagnostics via conguration software of the controller
SIRIUS 3RW5 PROFINET communication modules
Equipment Manual, 05/2021, A5E35631297002A/RS-AD/004 75