Enclosure for ET 200iSP in Zone 21
The ET 200iSP must be installed in a dust-proof (certi󹪝ed) enclosure with degree of protection
IP6X (according to directive 2014/34/EU for category 2D). Further requirements (surface
temperature, for example) can be found in the certi󹪝cation document for the enclosure. See
Appendix "Article numbers (Page 419)".
Remove dust deposits from the enclosure and its immediate environment at regular intervals; in
other words, always install the enclosure in a location with easy access for cleaning.
&ODMPTVSF
;POF`
$BCMFHMBOE$BCMFHMBOE
*OQVUBOEPVUQVU1PXFS
TVQQMZ
130'*#64
34*4
*1Y
&YJ
Figure 5-2 Enclosure for ET 200iSP in Zone 21
Installing
5.1 Installation rules
ET 200iSP
Operating Instructions, 11/2022, A5E00247483-AK 103