Measuring ranges for resistance-based sensors: 600 Ω absolute and 1000 Ω absolute
Table 14-14 SIMATIC S7 format: Measuring ranges 600 Ω absolute and 1000 Ω absolute
Measuring range
600 Ω
Measuring
range 1000 Ω
Units Range
Decimal Hexadeci‐
mal
> 705.53 > 1175.89 32767 7FFF
H
Overow
705.53 1175.89 32511 7EFF
H
Overrange
: : : :
600.02 1000.04 27649 6C01
H
600.00 1000.00 27648 6C00
H
450.00 750.00 20736 5100
H
: : : : Nominal range
0.00 0.00 0 0
H
(negative values are physically impossi‐
ble)
-1 FFFF
H
Underrange
1
: :
-4864 ED00
H
-32768 8000
H
Underow
1
1
If the connection is faulty
Measuring ranges for resistance thermometers Pt 100 standard
Table 14-15 SIMATIC S7 format: Measuring ranges Pt 100 standard in °C and °F
Pt 100
standard in
°C (1 digit =
0.1 °C)
Units Pt 100
Standard in
°F (1 digit =
0.1 °F)
Units Range
Decimal Hexa‐
decimal
Decimal Hexa‐
decimal
> 1000.0 32767 7FFF
H
> 1832.0 32767 7FFF
H
Overow
1000.0
:
850.1
10000
:
8501
2710
H
:
2135
H
1832.0
:
1562.1
18320
:
15621
4790
H
:
3D05
H
Overrange
850.0
:
-200.0
8500
:
-2000
2134
H
:
F830
H
1562.0
:
-328.0
15620
:
-3280
3D04
H
:
F330
H
Nominal range
-200.1
:
-243.0
-2001
:
-2430
F82F
H
:
F682
H
-328.1
:
-405.4
-3281
:
-4054
F32F
H
:
F02A
H
Underrange
< - 243.0 -32768 8000
H
< -405.4 -32768 8000
H
Underow
Analog electronic modules
14.8 Representation of analog values
ET 200iSP
Operating Instructions, 11/2022, A5E00247483-AK 379