Communication
2.3 Modbus communication
SIMOCODE pro - Communication
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
107
Request message frame
Slave
address
Function
code
Start
address
read
operation
Number
of
registers
(read
access)
Start
address
write
operation
Number
of
register
N (write
access)
Number
of bytes
(write
access)
Data
(write
access)
CRC
1 byte
1 byte
2 bytes
2 bytes
2 bytes
2 bytes
1 byte
Nx2bytes
2 bytes
0x10 0x17 0x04 0x00 0x0004 0x00
0x00
0x00
0x01
0x02 0x00
0x24
Response message frame
Slave address
Function code
Number_bytes
Data
CRC
1 byte
1 byte
1 byte
Nx2 bytes
2 bytes
0x10
0x17
0x08
0x00 0x00
0x00 0x00
Note
"Read/Write Multiple Registers" function
The "Read/Write Multiple Registers" function cannot be used for writing parameter values via
Modbus.
Writing of parameter values results in an execution time in SIMOCODE for writing
parameters to the internal memory during wh
ich this SIMOCODE cannot respond to a
communication request and/or the command "Read/Write Multiple Registers" cannot be
concluded.

Table of Contents

Other manuals for Siemens SIMOCODE pro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE pro and is the answer not in the manual?

Siemens SIMOCODE pro Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE pro
CategoryControl Unit
LanguageEnglish

Related product manuals