Tables, data records
3.5 Modbus data tables
SIMOCODE pro - Communication
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
301
3.5.2.14
Extended device parameters 1
Read access to the device parameters is possible from the register memory area with
function codes 03 and 04.
Individual parameter data (marked with the motor symbol in the "Info" column) can be written
via Modbus RTU via the register memory area with function codes 06 and 16. This function
can be used to adjust settings such as the rated motor current during operation of the motor.
The "SIMOCODE ES (TIA Portal)" software is nonetheless required for full parameterization
of the SIMOCODE pro V Modbus devices (see also Chapter "Commissioning with
Modbus RTU" in the SIMOCODE pro System Manual
(https://support.industry.siemens.com/cs/ww/en/view/109743957)).
Max. data length per access: 72 registers.
Table 3- 85 Extended device parameters 1
Input/holding register
Designation
Type
Range
Unit
Default
Comments
Access
1)
Info
Address
high/
low
Bit
0x4380
Coordination
Byte
[4]
r
Part - Bit parameters
0x4382 high 0 3UF50 compatibility
mode
Bit 0, 1 0 r
1 3UF50 operating
mode
Bit 0, 1 0 0 = DPV0
1 = DPV1
r
2
Reserved
Bit
0
r
3
Reserved
Bit
0
r
4
Reserved
Bit
0
r
5
Reserved
Bit
0
r
6
Reserved
Bit
0
r
7
Reserved
Bit
0
r
low
0
Reserved
Bit
0
r
1 Voltage measuring -
Type of load
Bit 0, 1 0 0 = 3-phase
1 = 1-phase
r
2
OPD - Warnings
Bit
0, 1
0
0 = Do not
display
1 = Display
r from E03
3 OPD - Faults Bit 0, 1 1
4 AM1 - Measuring
range input
Bit 0, 1 0 0 = 0 ... 20 mA
1 = 4 ... 20 mA
r
5 AM1 - Measuring
range
Output
Bit 0, 1 0 r
6
Reserved
Bit
0
r
7
Reserved
Bit
0
r