Tables, data records
3.4 Tables, PROFINET data records
SIMOCODE pro - Communication
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
273
3.4.2.17
Data record 140 - Marking 2
For limit monitors, and monitoring functions of the temperature and analog modules, user-
specific texts can be configured for marking.
You can access the following texts via data record 140:
Limit 5 and 6
TM2 warnings T> / trip T>
AM2 warning / trip 0/4-20mA<>.
Note
Changing the marking
Each change to the marking requires that the communication interfac
e be restarted when
the web server is active. A new start interrupts all Ethernet and PROFINET links and
reestablishes them afterward.
Table 3- 68 Data record 140 - Marking 2
Byte.Bit
Designation
Type
Information
0.0 Coordination Byte[4]
4.0
Reserved
10.0
Marking limit 5
Byte[10]
20.0
Marking limit 6
Byte[10]
30.0
Marking - TM2 warning T>
Byte[10]
40.0
Marking - TM2 trip T>
Byte[10]
50.0
Marking - Warning 0/4-20 mA>
Byte[10]
60.0
Marking - Warning 0/4-20 mA<
Byte[10]
70.0
Marking - Trip 0/4-20 mA>
Byte[10]
80.0
Marking - Trip 0/4-20 mA>
Byte[10]
90.0
Reserved
Byte[110]