Tables, data records   
3.5 Modbus data tables 
  SIMOCODE pro - Communication 
282  Function Manual, 11/2018, A5E40508495002A/RS-AC/003 
 
Read-only access to the device diagnostics is possible from the register memory area with 
function codes 03 and 04, or the coil memory area with function codes 01 and 02. 
Max. data length per access: 16 registers. 
Table 3- 76  Device diagnostics 
Discrete 
input / coil 
address 
0x1C00 
 
 
 
 
 
 
 
low  Bit 
0x1C00
 
Reserved
 
r
 
high 
 
Bit 
Status - PE command Start_Pause pending 
Status - PE energy saving mode active 
0x1C01 
 
 
 
 
 
 
 
 
 
low  Bit 
Status - Interlocking time active 
0x1C17  Status - Change-over pause active  r 
high 
 
Bit 
Status - Runs in open direction 
0x1C19  Status - Runs in close direction  r