Tables, data records
3.6 EtherNet/IP data tables
SIMOCODE pro - Communication
316 Function Manual, 11/2018, A5E40508495002A/RS-AC/003
3.6.3
Message Router object
The Message Router object is defined by CIP. It does not possess any class or instance
attributes, but simply transfers explicit messages to the relevant objects.
3.6.4
Assembly object
The following information applies to the Assembly object of the SIMOCODE pro V
EtherNet/IP device:
Class code: 0x04
Class attributes: 1, 2, 3
Number of instances: 13.
Instance 2: Output assembly basic overload from ODVA Profile
The tables below describe in each case the format of attribute 3 of the relevant assembly
instance.
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Reserved
Reserved
Reserved
Reserved
Reserved
Fault Reset
Reserved
Reserved
Instance 50: Input assembly basic overload from ODVA Profile
The table below describes the format of attribute 3:
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Faulted / Trip
Instance 51: Input assembly extended overload from ODVA Profile
The table below describes the format of attribute 3:
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Warning
Faulted / Trip

Table of Contents

Other manuals for Siemens SIMOCODE pro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE pro and is the answer not in the manual?

Siemens SIMOCODE pro Specifications

General IconGeneral
Protection ClassIP20
Mounting TypeDIN rail mounting
Rated Operational Voltage24 V DC
Rated CurrentUp to 820 A
Protection FunctionsOverload, short-circuit, phase failure, asymmetry, ground fault, motor stall
Operating Temperature Range-25°C to +60°C
Communication ProtocolsPROFIBUS DP, PROFINET, Modbus RTU
Analog OutputsUp to 2
Temperature MonitoringPTC/KTY, RTD (PT100/PT1000)
Digital OutputsRelay outputs, Solid-state outputs
Analog Inputs0/4-20mA, PT100/PT1000