Tables, data records   
3.5 Modbus data tables 
  SIMOCODE pro - Communication 
294  Function Manual, 11/2018, A5E40508495002A/RS-AC/003 
 
Read access to the device parameters is possible from the register memory area with 
function codes 03 and 04. 
Individual parameter data (marked with the motor symbol in the "Info" column) can be written 
via Modbus RTU via the register memory area with function codes 06 and 16. This function 
can be used to adjust settings such as the rated motor current during operation of the motor. 
Max. data record length per access: 46 registers. 
The "SIMOCODE ES (TIA Portal)" software is nonetheless required for full parameterization 
of the SIMOCODE pro V Modbus devices (see also Chapter "Commissioning with 
Modbus RTU" in the SIMOCODE pro – System Manual 
(https://support.industry.siemens.com/cs/ww/en/view/109743957)). 
Table 3- 84  Basic device parameter 1  
0x4180     
  Byte 
          r 
0x4182     
Byte 
          r 
0x4186 
 
high  0  No configuration 
Bit  0, 1    0      r 
1  Startup 
parameter block 
Bit  0, 1    0      r 
2  TEST/RESET 
Bit  0, 1    0      r 
3  Bus and 
PLC/PCS - Reset 
Bit  0, 1    0  0 = Manual 
  r 
low  0  Diagnostics for 
Bit  0, 1    0      r 
1  Diagnostics for 
process warnings 
Bit  0, 1    1      r 
2  Diagnostics for 
Bit  0, 1    1      r 
3  Diagnostics for 
device faults 
Bit  0, 1    1      r 
7  PLC/PCS 
Bit  0, 1    1      r