Communication   
2.1 PROFIBUS communication 
  SIMOCODE pro - Communication 
18  Function Manual, 11/2018, A5E40508495002A/RS-AC/003 
 
Diagnostics data and alarms 
Diagnostic data and interrupts - overview 
Diagnostics data contains important information about the status of SIMOCODE pro. This 
information simplifies troubleshooting. 
Unlike cyclic data, the diagnostics data is only transmitted to the master module if it changes. 
PROFIBUS DP differentiates between:  
●  Standard diagnostics  
●  Status information  
●  Channel-related diagnostics  
●  DPV1 process and diagnostic interrupts.  
Configuring diagnostic response  
In SIMOCODE pro, you can set which diagnostic events trigger the transmission of 
diagnostics data or interrupts to the PLC: 
●  Diagnostics for device faults, e.g. parameterization errors, hardware faults  
●  Diagnostics for process faults: 
In the case of events identified as "S" in the column headed "DP diagnostics" in the "Data 
record 92 - Diagnostics" table, the diagnostics data or interrupts are transferred to the 
PLC.  
●  Diagnostics for process warnings: 
In the case of events identified as "W" in the column headed "DP diagnostics" in the 
"Data record 92 - Diagnostics" table, the diagnostics data or interrupts are transferred to 
the PLC.  
●  Diagnostics for process events: 
In the case of events identified as "M" in the column headed "DP diagnostics" in the "Data 
record 92 - Diagnostics" table, the diagnostics data or interrupts are transferred to the 
PLC.  
Set the response in dialog 
Device Parameters > Bus Parameters > Diagnosis 
.