Tables, data records
3.4 Tables, PROFINET data records
SIMOCODE pro - Communication
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
229
3.4.2.7
Data record 92 - Device diagnostics
Table 3- 58 Data record 92 - Diagnostics
Byte.Bit
Designation
Information
PNIO
diagnostic
status **)
PNIO error
number (channel
error type)
Error no.
0.0
Reserved
1.0 Status
information -
General
Status - General fault
1.1
Status - General warning
1.2
Status - Device
1.3
Status - Bus
1.4
Status - PLC/PCS
1.5
Status - Motor current flowing
IM UM(+)
1.6
Reserved
1.7
Reserved
2.0 Status
information -
Receive
Status - ON<< Dependent on
the control
function
2.1
Status - ON<
2.2
Status - Off
2.3
Status - ON>
2.4
Status - ON>>
2.5
Status - Start active
2.6 Status - Interlocking time active All reversing
starters and
positioners
2.7 Status - Change-over pause
active
Star-delta
starter,
Dahlander
starter,
pole-changing
starter
3.0
Status - Runs in open direction
Dependent on
the control
function
3.1
Status - Runs in close direction
3.2
Status - FC
3.3
Status - FO
3.4
Status - TC
3.5
Status - TO
3.6
Status - Cold starting (TPF)
1
0x1009
3.7
Status - OPO
4.0
Status - Auto mode
4.1 Status
information -
Protection
Status - Emergency start
executed
IM UM(+) 1 0x1031

Table of Contents

Other manuals for Siemens SIMOCODE pro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE pro and is the answer not in the manual?

Siemens SIMOCODE pro Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE pro
CategoryControl Unit
LanguageEnglish

Related product manuals