Tables, data records
3.3 Tables, PROFIBUS data records
SIMOCODE pro - Communication
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
181
3.3.2.12
Data record 131 - Basic device parameters 2 (plug binary)
Table 3- 34 Data record 131 - Basic device parameters 2
Byte.Bit
Designation (PRM group)
Type
Range
Default
Note
Information
0.0
Reserved
Byte[4]
4.0
Byte parameters (40)
4.0
BU - Output 1
Byte
0 - 255
0
BU0 BU1 BU2(+)
5.0 BU - Output 2 Byte 0 - 255 0 BU0 BU1 BU2(+)
6.0
BU - Output 3
Byte
0 - 255
0
BU1 BU2(+)
7.0
Reserved
Byte
0
8.0
OP - LED green 1
Byte
0 - 255
0
OP OPD
9.0
OP - LED green 2
Byte
0 - 255
0
OP OPD
10.0
OP - LED green 3
Byte
0 - 255
0
OP OPD
11.0
OP - LED green 4
Byte
0 - 255
0
OP OPD
12.0
OP - LED yellow 1
Byte
0 - 255
0
OP
13.0
OP - LED yellow 2
Byte
0 - 255
0
OP
14.0
OP - LED yellow 3
Byte
0 - 255
0
OP
15.0
Reserved
Byte
0
16.0 Cyclic send - Bit 0.0 Byte 0 - 255 105 Default: Status
- ON<
BU0 BU1 BU2(+)
17.0 Cyclic send - Bit 0.1 Byte 0 - 255 106 Default: Status
- Off
BU0 BU1 BU2(+)
18.0 Cyclic send - Bit 0.2 Byte 0 - 255 107
Default: Status
- ON>
BU0 BU1 BU2(+)
19.0 Cyclic send - Bit 0.3 Byte 0 - 255 128 Default: Event
- Overload
operation
BU0 BU1 BU2(+)
20.0 Cyclic send - Bit 0.4 Byte 0 - 255 110 Default: Status
- Interlocking
time active
BU0 BU1 BU2(+)
21.0 Cyclic send - Bit 0.5 Byte 0 - 255 120
Default: Status
- Auto mode
BU0 BU1 BU2(+)
22.0 Cyclic send - Bit 0.6 Byte 0 - 255 96
Default: Status
- General fault
BU0 BU1 BU2(+)
23.0 Cyclic send - Bit 0.7 Byte 0 - 255 97 Default: Status
- group
warning
BU0 BU1 BU2(+)
24.0
Cyclic send - Bit 1.0
Byte
0 - 255
0
BU0 BU1 BU2(+)
25.0
Cyclic send - Bit 1.1
Byte
0 - 255
0
BU0 BU1 BU2(+)
26.0
Cyclic send - Bit 1.2
Byte
0 - 255
0
BU0 BU1 BU2(+)
27.0
Cyclic send - Bit 1.3
Byte
0 - 255
0
BU0 BU1 BU2(+)
28.0
Cyclic send - Bit 1.4
Byte
0 - 255
0
BU0 BU1 BU2(+)
29.0
Cyclic send - Bit 1.5
Byte
0 - 255
0
BU0 BU1 BU2(+)
30.0
Cyclic send - Bit 1.6
Byte
0 - 255
0
BU0 BU1 BU2(+)
31.0
Cyclic send - Bit 1.7
Byte
0 - 255
0
BU0 BU1 BU2(+)

Table of Contents