Tables, data records
3.3 Tables, PROFIBUS data records
SIMOCODE pro - Communication
172 Function Manual, 11/2018, A5E40508495002A/RS-AC/003
3.3.2.9
Data record 94 - measured values
Table 3- 31 Data record 94 - Measured values
Byte.Bit
Designation
Type
Range
Unit
Information
0.0
Reserved
Byte[4]
4.0
Thermal motor model
Byte
0 - 255
See
2
)
IM UM(+)
5.0
Phase unbalance
Byte
0 - 100
1 %
IM UM(+)
6.0 cos phi Byte 0 - 100 1 % UM(+)
7.0
Reserved
Byte[5]
12.0
Max. current I_max
Word
0 - 65535
1 % / I
s
IM UM(+)
14.0
Current I_L1
Word
0 - 65535
1 % / I
s
IM UM(+)
16.0
Current I_L2
Word
0 - 65535
1 % / I
s
IM UM(+)
18.0
Current I_L3
Word
0 - 65535
1 % / I
s
IM UM(+)
20.0
Last trip current
Word
0 - 65535
1 % / I
s
IM UM(+)
22.0
Time to trip
Word
0 - 65535
100 ms
IM UM(+)
24.0
Cooling down period
Word
0 - 65535
100 ms
IM UM(+)
26.0
Voltage U_L1
Word
0 - 65535
1 V
UM(+)
28.0
Voltage U_L2
Word
0 - 65535
1 V
UM(+)
30.0
Voltage U_L3
Word
0 - 65535
1 V
UM(+)
32.0
AM output
Word
0 - 32767
See
1
)
AM
34.0
AM - Input 1
Word
0 - 32767
AM
36.0
AM - Input 2
Word
0 - 32767
AM
38.0
Reserved
40.0
TM - Max. temperature
Word
0 - 65535
1 K see
3)
TM MM
42.0
TM - Temperature 1
Word
0 - 65535
1 K see
3)
TM MM
44.0
TM - Temperature 2
Word
0 - 65535
1 K see
3)
TM
46.0 TM - Temperature 3 Word 0 - 65535 1 K see
3)
TM
48.0
EM+
4)
- ground-fault current
Word
0 - 65535
1 mA
MM EM(+)
50.0 EM+
4)
- last tripping current Word 0 - 65535 1 mA MM EM(+)
52.0
Active power P
D-word
0 - 0xFFFFFFFF
1 W
UM(+)
56.0
Apparent power S
D-word
0 - 0xFFFFFFFF
1 VA
UM(+)
60.0
Reserved
Byte[14]
132.0
Frequency
Word
0 - 65535
0.01 Hz
UM+
134.0
Reserved
136.0
Reserved
138.0
Reserved
140.0
Reserved
Byte[4]
144.0
Current I_max_F (float)
Float
1 A
UM+
148.0
Current I_avg_F
Float
1 A
UM+
152.0
Current I_L1_F
Float
1 A
UM+
156.0
Current I_L2_F
Float
1 A
UM+
160.0
Current I_L3_F
Float
1 A
UM+
164.0
Active power P_F
Float
1 W
UM+

Table of Contents

Other manuals for Siemens SIMOCODE pro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE pro and is the answer not in the manual?

Siemens SIMOCODE pro Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE pro
CategoryControl Unit
LanguageEnglish

Related product manuals