Tables, data records
3.5 Modbus data tables
SIMOCODE pro - Communication
300 Function Manual, 11/2018, A5E40508495002A/RS-AC/003
Input/holding register
Designation
Type
Range
Unit
Default
Comments
Info
Access
1)
Address
high/low
Bit
0x41A2 Counter 1 value Word 0 ...
65535
0
r/w
0x41A3 Counter 2 value Word 0 ...
65535
0
r/w
0x41A4 EM+ - trip level Word 30 ...
40000
1 mA 1000
r/w
0x41A5 EM+ - warning
level
Word 30 ...
40000
1 mA 500
r/w
Part - D word
parameter
0x41A6 Operator control
enables
Bit
[32]
0 ...
1 ... 1B
0 ... 0B r
0x41A8 Motor protection -
Set current Is1
2)
D
word
10
mA
30 IM UM
(+)
r/w
0x41AA Motor operating
hours level >
D
word
0 ...
0xFFF
FFFFF
1 s 0
r/w
0x41AC
Reserved
D-
word
0
r