Tables, data records
3.5 Modbus data tables
SIMOCODE pro - Communication
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
299
0x4196
high Blocking delay Byte 0 ...
255
100
ms
5 IM UM
(+)
r/w
low Monitoring the
number of starts -
Byte 1 ...
255
1
r/w
0x4197
low EM+ - warning
delay
Byte 0 ...
255
100
ms
1
r/w
0x4198
high Truth table 1
type 3I/1O
Byte 0 ...
111111
11B
0 r
low Truth table 2
type 3I/1O
Byte 0 ...
111111
0 r
0x4199
high Truth table 3
type 3I/1O
Byte 0 ...
111111
0 r
0x419A Motor protection -
Cooling down
period
Word 600 ...
65535
100
ms
3000 IM UM
(+)
r/w
0x419B Motor protection -
Pause time
Word 0 ...
65535
100
ms
0 0 = Disabled IM UM
(+)
r/w
0x419C Execution time Word 0 ...
65535
100
ms
10 0 = Disabled
r/w
0x419D Monitoring the
number of starts -
Time range for
Word 0 ...
65535
1 s 0
r/w
0x419E Monitoring the
number of starts -
Word 0 ...
65535
1 s 0
r/w
0x419F Motor stop time
level >
Word 0 ...
65535
1 h 0
r/w
0x41A0 Timer 1 value Word 0 ...
65535
100
ms
0
r/w
0x41A1 Timer 2 value Word 0 ...
65535
100
ms
0
r/w